LPHW Units - Performance Data



Trench Heating Performance Data
Model Position Finned Element Heater Heater Corrected Corrected Uncorrected
reference of Elements Quantity & dim WIDTH HEIGHT 82-71/20 80-60/20 Output
T1 Offset 1/35 x 75 150 90 161 135 177
T2 Central 2/35 x 75 250 90 303 255 334
T2.O Offset 2/35 x 75 225 90 285 239 313
T3.O Offset 1/75 x 50 150 115 324 272 356
T4 Central 2/75 x 50 250 115 513 431 564
T4.O Offset 2/75 x 50 225 115 491 412 540
T5.O Offset 1/75 x 75 150 150 420 353 462
T5.OR Offset 1/75 x 75 150 150 435 368 478
T5.OSV Offset 1/75 x 75
+1/75 x 50
150 200 460 389 505
T6 Central 2/75 x 75 250 150 691 585 760
T6.O Offset 2/75 x 75 225 150 665 563 732
T6.OV Offset 2/75 x 75 150 250 475 402 522
T7 Central 1/108 x 50 225 115 393 332 432
T7.O Offset 1/108 x 50 200 115 354 299 389
T8 Central 1/108 x 75 225 150 438 371 482
T8.O Offset 1/108 x 75 200 150 425 360 468
T9 Central 1/108 x 108 225 185 512 433 563
T9.O Offset 1/108 x 108 200 185 498 421 547
T10 Central 2/108 x 50 350 115 561 475 617
T10.O Offset 2/108 x 50 300 115 538 455 591
T11 Central 2/108 x 75 350 150 717 602 788
T11.O Offset 2/108 x 75 300 150 701 593 771
T12 Central 2/108 x 108 350 185 984 832 1081
T12.O Offset 2/108 x 108 300 185 959 810 1053
T12.OV Offset 2/108 x 108 175 300 575 486 631
T13 Central 4/75 x 75 250 225 1461 1235 1605
T13.O Offset 4/75 x 75 225 225 1390 1175 1527
T13.OSA Offset 2/75 x 75
+2/75 x 35
225 190 907 766 996
T13.OSB Offset 2/75 x 75
+2/75 x 50
225 200 978 826 1074
T14 Central 4/108 x 108 350 300 1996 1688 2193
T14.O Offset 4/108 x 108 300 300 1901 1608 2089
T15.O Offset 6/75 x 75 325 235 1760 1488 1934
T15.V Central 6/75 x 75 278 325 1390 1175 1527
T16.O Offset 3/75 x 75
+3/75 x 35
325 175 1278 1081 1404
   
Corrected Heat outputs have been calculated at 1 mtr/sec velocity